MULTI-FUNCTION DIGITAL CONTROLLER
FX32P
RS485 Retrans4~20mA
Pressure Switch Controller
c
1 2 3 4 5 6 7 8 9 10 11
COM mA +12V
L2L1
AC100 - 240V~
SENS OR
50/60Hz
FX32P
OPTION
MODULE
L1
L2
N1 N2 N3 N4
N1,2 : 10A, 250V
N3,4 : 5A, 250V
+
2wire
3wire
N1 : decrease pressure / increase pressure
#1 ON/OFF output, event output
N2 : decrease pressure / increase pressure
#2 ON/OFF output, event output
N3 : decrease pressure / increase pressure
#3 ON/OFF output, event output
N4 : decrease pressure / increase pressure
#4 ON/OFF output, event output
FX32P– 00 : Basic model
FX32P– R4 : Add on RS485 communication (MODBUS)
FX32P– A1 : Add on 4~20mA transmission output
Main-
Function
Input/output
Models
Power Supply
Output controllable based on measured pressure value (increase and decrease),
alternative operation available between freezing exclusive model and booster,
pump unit control exclusive model, RS485 communication (MODBUS)
AC100~240V, 50/60Hz, Max. 4VA, screw bolt terminals
relay output : 4 point, Input sensor : 1 point (including power supply)
Sensor Spec
4~20mA (2 wire or 3 wire)
FX32F
NTC Heating Cooling RS485
Fan Coil Unit Controller
FX32F
AC100-240V~
50/60Hz
FAN
LO MD HI COM
B/T
AMB
TEMP
1 2 3 4 5 6 7 8 9 10 11 12 13
2A 250Vac
POWER
OPTION
MODULE
L2 B2 B1
G G
L1
AMB. TEMP
SENSOR
COIL TEMP
SENSOR
LO : low wind speed on/off output
MD : midium wind speed on/off output
HI : high wind speed on/off output
G : signal input common terminal
B1 : Ambient temperature sensor input
B2 : coil temerature sensor input
Main-
Function
Input/output
Models
Power Supply
3 stage fan speed controllable, 4 kind (stop/high/middle/low) airow choosable,
unication of temp. control function, data backup, self diagnostic, RS485
communication (MODBUS)
AC100~240V, 50/60Hz, Max. 4VA, connector
relay output : 3 point (airow control),
Temp. sensor input : 2 point (room & water)
Sensor Spec
DPR-TH1 : NTC 5k, ±0.3°C at 25°C (-50°C~105°C)
FX32F– 00 : Basic model
FX32F– R4 : Add on RS485 communication (MODBUS)
comp : main motor on/off output
sol : LOAD SOL ON/OFF output
B1 : pressure sensor input signal
B2 : temperature sensor input signal
ID1 : control output interlock signal(OCR, EMSW)
ID2 : remote run / stop control signal
FX32A
RS485NTC Retrans4~20mA
Air Compressor Controller
Main-
Function
Input/output
Models
Power Supply
Embedded run/stop switch, motor on/off, load run, auto-stop, manual
stop, operation delay, load delay, embedded timer,
pressure/temerature high level, temperature low level (standby for
starting), interlock input signal (emergency switch, OCR reverse phase),
Usable thermometer and manometer, RS485 communication
(MODBUS)
AC100~240V, 50/60Hz, Max. 4VA, screw bolt terminals
Relay output : 2 point (motor, SOL)
Digital input : 2 point (interlock, remote control)
Temp. sensor input : 1 point (discharge air temperature)
Pressure sensor input : 1 point (discharge air pressure)
Sensor Spec
DPR-TH2 : NTC 10k, ±0.3°C at 25°C (-50°C~150°C)
FX32A-351
NTC RS485 Retrans4~20mA
Air Compressor Controller
1 2 3 4 5 6 7 8 9 10 11
+VDCCOMB2B3ID1
FX32A-351
B1
OPTION
MODULE
L1
L2
L2L1
AC100 - 240V ~
50/60Hz
3A 250Vac
C1 C2 C
ID1 : remote run/stop signal
C1 : COMP1 motor ON/OFF output
C2 : COMP2 motor ON/OFF output
B1 : pressure sensor input signal
B2 : COMP1 temp. sensor input signal
B3 : COMP2 temp. sensor input signal
FX32A– 00 : Basic model
FX32A– R4 : Add on RS485 communication (MODBUS)
FX32A– A1 : Add on 4~20mA transmission output
FX32A– R2 : Add on RS232 communication
Main-
Function
Input/output
Models
Power Supply
Embedded run/stop switch, motor on/off, load run, auto-stop, manual
stop, operation delay, load delay, embedded timer,
pressure/temerature high level, temperature low level (standby for
starting), interlock input signal (emergency switch, OCR reverse phase),
Usable thermometer and manometer, RS485 communication(MODBUS)
AC100~240V, 50/60Hz, Max. 4VA, screw bolt terminals
Relay output : 2 point (motor, SOL)
Digital input : 2 point (interlock, remote control)
Temp. sensor input : 1 point (discharge air temperature)
Pressure sensor input : 1 point (discharge air pressure)
Sensor Spec
Pressure Sensor : 0~16 bar (4~200mA)
DPR-TH2 : NTC 10k, ±0.3°C at 25°C (-50°C~150°C)
FX32A-351-00 : Basic model
FX32A-351-R4 : Add on RS485 communication (MODBUS)
FX32A-351-A1 : Add on 4~20mA transmission output
FX32A-351-R2 : Add on RS232 communication
FX Series
SENSETE°CH®
CWC HEAT-EDGE®
RAINBOW
SHIMADEN
PR ELECTRONICS KIMO SEKONIC
HUBA
KAISE
OHKURA CORDEX
FRIED ELECTRIC
DOTECH
V-A5
Sensing
Technology
Corporation
457-B Boni Avenue New Zaniga Mandaluyong City
Tel No.
532-0088
Fax No.
531-7387
www.heatsenze.com
Zobrazit stránku 6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15